Zoning fundamentalsExplainer

Building height, explained

A height limit sounds simple until you ask where to measure from and to. The answer depends on the roof, on the ground around the building, and on a short list of things allowed to rise above the line.

How Chicago measures it

heightgradetop floor’s ceiling

pitched roof: grade → midpoint of eave and ridge

The measurement rules below are Chicago’s, from Title 17, linked to our hosted zoning code. Other cities measure from and to different points; the “Elsewhere” note compares a few. Drawings are at true vertical scale.

Definition

What “building height” means

Building height is a vertical distance from a fixed starting point, grade, to a fixed point on the building. Zoning codes differ mostly on the second point: the top of the roof, the top of the parapet, the ceiling of the top floor, or somewhere on a sloped roof.

Where the measurement starts: grade

Chicago defines grade as the curb level next to the front property line or the mean finished grade along the building’s exterior walls, whichever is higher §17-17-0265. On a lot that sits below the street, height is still measured from the curb.

Stories and floors

A story is the space between one floor and the next §17-17-02169. A basement counts as a story only when more than half of its floor-to-ceiling height is above grade. For the height rule, a “floor” is any enclosed area with at least 6 ft 9 in of headroom §17-17-0311-A.

Measurement

Flat roofs, pitched roofs, and what sticks up

Chicago measures to the underside of the top floor’s ceiling joists on a flat roof, and to the mean height between eaves and ridge on a gable, hip, mansard or gambrel roof §17-17-0311-A. That is a Chicago choice, not a national standard.

Flat roof

To the top ceiling

A three-story flat-roofed building. Height is measured from grade to the underside of the top floor's ceiling joists, 35 feet here; the roof structure and parapet above it are not counted. 35 ft

Three floors of 12 ft put the top ceiling at 35 ft. The roof deck and parapet above it (gray) are not part of the measured height.

Pitched roof

To the midpoint

A gable-roofed house with eaves at 26 feet and the ridge at 38 feet. Its height is the midpoint, 32 feet, marked by a dashed line across the gable end. 32 ft

Eaves at 26 ft and a ridge at 38 ft measure 32 ft, so a ridge can rise well above a 30 ft limit.

Rooftop

Allowed above the limit

The flat-roofed building with a stair enclosure on the roof, set back 20 feet from the front wall nearest the viewer. In residential districts an enclosure like this may rise above the height limit if it meets the size and setback limits. 20 ft35 ft

A stair enclosure to a roof deck may exceed the limit if it is set back 20 ft from the front wall and stays within size limits.

Same footprint in each drawing, at true vertical scale. The measured height is the blue dimension; everything above it is either excluded by the measurement rule or allowed above the limit.

What may rise above the height limit

  • Stair and elevator enclosures serving an occupiable roof, and elevator penthouses §17-17-0311-C. In R districts: set back 20 ft from the front building line, and a stair-only enclosure up to 200 sq ft and 13 ft tall; with an elevator, up to 500 sq ft and 19 ft 6 in. These enclosures also don’t count as floor area for FAR.
  • Solar panels on a flat roof, up to 9 ft tall or 5 ft above the parapet, whichever is lower §17-17-0311-B.
  • Pergolas and trellises on a roof deck, set back 20 ft from the front on buildings under 80 ft, up to 11 ft above the deck or 8 ft above the parapet, whichever is greater.
  • Rooftop wind turbines, set back 20 ft and up to 15 ft above the roof or parapet.

On a corner lot, a rooftop enclosure must also be set back from the street-facing side wall by half the distance between the side building lines §17-17-0311-C.

Chicago

Height limits in Chicago

Residential districts set a single limit for residential buildings, with a few adjustments for lot width and accessible units §17-2-0311. Principal nonresidential buildings in R districts have no listed height limit.

DistrictHeight limitNotes
RS-130 ft
RS-230 ft
RS-330 ft
RT-3.535 ft
RT-438 ft42 ft if at least 25% of units are Type A (buildings of 19 units or fewer)
RM-4.545-47 ft45 ft with lot frontage under 32 ft, 47 ft at 32 ft or more
RM-545-47 ft45 ft with lot frontage under 32 ft, 47 ft at 32 ft or more
RM-5.547-60 ft47 ft with lot frontage of 75 ft or less, 60 ft above that
RM-6No limit (PD review)No fixed limit; tall buildings need a planned development
RM-6.5No limit (PD review)No fixed limit; tall buildings need a planned development

Residential buildings in R districts. Limits come from the same rule table the LotGrade analyzer uses; each district links to its Field Guide page.

Business and commercial districts

In B and C districts the limit depends on the dash number, the lot frontage, and whether the building has ground-floor commercial space that meets §17-3-0305 §17-3-0408-A. A lot with more than one frontage uses the shortest.

District≤ 25 ft25–50 ft50–99.9 ft100 ft +
Dash 1, 1.538383838
Dash 247 / 4550 / 4550 / 4550 / 45
Dash 350 / 5055 / 5065 / 6065 / 60
Dash 550 / 5055 / 5070 / 6580 / 75

Maximum height in feet, with / without qualifying ground-floor commercial space, by lot frontage. Dash 1 and 1.5 are 38 ft with commercial space; the table lists no figure without it. From §17-3-0408-A.

Going higher

  • Administrative adjustment: up to 10% more height §17-13-1003-L; in RS districts, up to 10% in exchange for a deeper rear setback, one foot per two extra feet of setback §17-13-1003-N.
  • Transit-served locations: B-3 and C-3 projects near CTA or Metra rail, or on listed bus corridors, can gain height through a Type 1 rezoning or a planned development §17-3-0408-B.
  • Planned developments: required above set thresholds — 110 ft in RM-6, 140 ft in RM-6.5, and 75 or 80 ft in dash-5 districts §17-8-0512. See zoning relief in Chicago.

Questions

Common questions

How is building height measured?

It varies by city. In Chicago, from grade to the underside of the top floor’s ceiling joists on a flat-roofed building, or to the midpoint between the eaves and the ridge on a gable, hip, mansard or gambrel roof (§17-17-0311-A). Seattle and Denver measure to the highest point of the structure, Los Angeles to the top of the roof or parapet, and New York City from a “base plane” tied to the curb and grade — so always check the local definition.

What is “grade” when measuring height?

The starting point differs by city. Chicago uses the curb level next to the front property line or the mean finished grade along the building’s exterior walls, whichever is higher (§17-17-0265). Raising the yard therefore raises the starting point; lowering it does not lower it below the curb.

Does a basement count as a story?

Codes differ. In Chicago it does when more than half of its floor-to-ceiling height is above grade (§17-17-02169). A garden unit sunk halfway into the ground usually is not a story; one that is mostly above ground is.

Can a rooftop deck stair or elevator go above the height limit?

Yes, within limits. In residential districts a stair-only enclosure set back at least 20 feet from the front building line may cover up to 200 sq ft and rise 13 feet above the top floor’s ceiling (§17-17-0311-C). Solar panels, pergolas and some wind equipment have their own allowances (§17-17-0311-B).

What is the height limit in Chicago?

30 feet in the RS districts, 35 in RT-3.5 and 38 in RT-4, 45 to 60 in the RM-4.5 through RM-5.5 districts, and no fixed limit in RM-6 and RM-6.5, where tall buildings go through a planned development. In business and commercial districts the limit depends on the dash number, the lot frontage and whether the ground floor has qualifying commercial space (§17-3-0408-A).

Can I get a height increase?

The Zoning Administrator can approve up to 10% more height in some cases (§17-13-1003-L), and in RS districts up to 10% in exchange for a deeper rear setback — one foot of height for every two feet of extra setback (§17-13-1003-N). Transit-served dash-3 sites can go higher through a rezoning or planned development (§17-3-0408-B).